high air velocity unit heater
The KFUH ECO2S series high air velocity unit heater is an efficient, dependable unit heater perfectly suited for high ceiling applications such as warehouses, parking garages and docks. The 5-speed, high-capacity motor and blower quietly delivers large volumes of air ranging from 775 to 1540 CFM minimum. With welded mounting channels on the unit, the heater may be mounted at any angle. Safety screens are provided at both the air intake and discharge aperture. The intake filter is replaceable. Thermostat may be ordered separately.
Perfectly suited for high ceiling applications such as warehouses, parking garages and docks. The 5-speed, high-capacity motor and blower quietly delivers large volumes of air ranging from 775 to 1540 CFM minimum.
Now That’s Smart!
With welded mounting channels on the unit, the heater may be mounted at any angle. Safety screens are provided at both the air intake and discharge aperture. The intake filter is replaceable. Thermostat may be ordered separately.
Contractor shall supply and install KFUH Series high air velocity unit heaters manufactured by King Electrical Mfg. Company. Heaters shall be of the wattage and voltage as indicated on the plans.
Transformer: Each unit is equipped with a heavy duty low voltage (24 Volt) transformer for the thermostat control circuit.
Heating Elements: Quick heating, long life Ni-Chrome elements are sized to provide proper watt density for maximum heat dissipation by fan-forced air convection currents.
Terminal Block: For single strike field wiring.
Low Voltage Terminal Block: For 24 Volt control.
Air Filter: Convenient access for replacement of standard 16” x 20” x 1” filter.
Motor: Long life, 48 frame capacitor run, thermally protected, permanently lubricated, direct drive motor (no belts to adjust or slip). This low noise, up to 5-speed motor is designed for maintenance-free operation.
Overcurrent Protection: 208 and 240 volt KFUH models have 60 amp circuit breakers with single strike terminal block. 480 volt models have single strike terminal block. Units over 48 amps have 60 amp fusing.
Limit Control: Integral automatic high temperature limit control in each heating element bank prevents the delivery of air at unsafe temperatures. 20-35 kW use a manual reset limit control to completely shut the unit heater off should overtemperature occur.
Fan Relay: Heavy duty fan relay standard with summer fan operation.
Approvals: UL (E41422)